Industrial Switches

PSU : HDR-60-24
-
Overview
Power Supply Industrial Switches Enterprise -
60W Industrial DIN Rail Power Supply – 24VDC/2.5A, Universal AC input, Plastic Case, -30°C ~ 70°C
HDR-60 is one economical slim 60W DIN Rail Industrial power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails.
HDR-60 is designed with plastic housing that can effectively prevent users from electrical hazards. With working efficiency up to 91%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. It is equipped with a constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, UL60950, EN60950-1, EN61558-2-16) make HDR-60 a very competitive power supply solution for industrial applications
Features
Universal AC input / Full range
Output: 24VDC / 2.5A / 60W
Efficiency: 90%
Plastic case design
Protections: Short circuit / Overload / Over voltage
DC output voltage adjustable
Cooling by free air convection
LED indicator for power on
Can be installed on DIN rail TS-35/7.5 or 15
Isolation class II
Operating temperature: -30℃ ~ 70℃
Safety standards: UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved
Dimension: 52.5x90x54.5mm (WxHxD)
Applications
Household control system
Building automation
Industrial Control System
Semiconductor Fabrication System
Factory Automation
Smart City Deployment
Electro-Mechanical Apparatus
Specifications
BASIC | |
MODEL | HDR-60-24 |
BRAND | MEANWELL |
WARRANTY | 2 Year |
OUTPUT | |
DC VOLTAGE | 24V |
RATED CURRENT | 2.5A |
CURRENT RANGE | 0 ~ 2.5A |
RATED POWER | 60W |
OUTPUT RIPPLE & NOISE (max.) | 150mVp-p |
VOLTAGE ADJ. RANGE | 20.6 ~ 29V |
VOLTAGE TOLERANCE | ±1.0% |
LINE REGULATION | ±0.5% |
LOAD REGULATION | ±1.0% |
SETUP, RISE TIME | 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load |
HOLD UP TIME (Typ.) | 30ms/230VAC 12ms/115VAC at full load |
INPUT | |
FREQUENCY RANGE | 47 ~ 63Hz |
VOLTAGE RANGE | 85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational ) |
EFFICIENCY (Typ.) | 90 |
AC CURRENT (Typ.) | 2.25A/115VAC 1.3A/230VAC |
INRUSH CURRENT (Typ.) | COLD START 30A/115VAC 60A/230VAC |
LEAKAGE CURRENT | <1mA / 240VAC |
PROTECTION | |
OVERLOAD | 105 ~ 160% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed |
OVER VOLTAGE | 30 ~ 36V |
PROTECTION TYPE | Shut down o/p voltage, re-power on to recover |
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover |
ENVIRONMENT | |
WORKING TEMP. | -30 ~ +70℃ (Refer to “Derating Curve”) |
WORKING HUMIDITY | 20 ~ 95% RH non-condensing |
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH |
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) |
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
SAFETY & EMC (Note 4) | |
SAFETY STANDARDS | UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved; Desi gn refer to TUV EN60950-1 |
WITHSTAND VOLTAGE | I/P-O/P:4KVAC |
ISOLATION RESISTANCE | I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH |
EMC EMISSION | Compliance to EN55032 (CISPR32) Class A, EN61000-3-2,-3 |
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A |
OTHERS | |
MTBF | 927.6K hrs min. MIL-HDBK-217F (25) |
DIMENSION | 52.5*90*54.5mm (W*H*D) |
PACKING | 190g;60pcs/12.4Kg/0.97CUFT |
DIMENSION | 35*90*54.5mm (W*H*D) |
PACKING | 0.12Kg;96pcs/12.5Kg/1.04CUFT |
Downloads