PSU : HDR-60-24

Category: Enterprise >

60W Industrial DIN Rail Power Supply – 24VDC/2.5A, Universal AC input, Plastic Case, -30°C ~ 70°C

  Ask a Question

OVERVIEW

HDR-60 is one economical slim 60W DIN Rail Industrial power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 52.5mm (3SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC (277VAC optional) and conforms to EN61000-3-2, the normal the European Union regulates for harmonic current.

HDR-60 is designed with plastic housing that it can effectively prevent user from electrical hazards. With working efficiency up to 91%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. It is equipped with constant current mode for overload protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, UL60950, EN60950-1, EN61558-2-16) make HDR-60 a very competitive power supply solution for industrial applications

FEATURES

Features

  • Universal AC input / Full range
  • Output: 24VDC / 2.5A / 60W
  • Efficiency: 90%
  • Plastic case design
  • Protections: Short circuit / Overload / Over voltage
  • DC output voltage adjustable
  • Cooling by free air convection
  • LED indicator for power on
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Isolation class II
  • Operating temperature: -30℃ ~ 70℃
  • Safety standards: UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved
  • Dimension: 52.5x90x54.5mm (WxHxD)

 

Applications

  • Household control system 
  • Building automation
  • Industrial Control System
  • Semiconductor Fabrication System 
  • Factory Automation
  • Smart City Deployment
  • Electro-Mechanical Apparatus

SPECIFICATIONS

BASIC
MODEL HDR-60-24
BRAND MEANWELL
WARRANTY 2 Year
OUTPUT
DC VOLTAGE 24V
RATED CURRENT 2.5A
CURRENT RANGE 0 ~ 2.5A
RATED POWER 60W
OUTPUT RIPPLE & NOISE (max.) 150mVp-p
VOLTAGE ADJ. RANGE 20.6 ~ 29V
VOLTAGE TOLERANCE ±1.0%
LINE REGULATION ±0.5%
LOAD REGULATION ±1.0%
SETUP, RISE TIME 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 30ms/230VAC 12ms/115VAC at full load
INPUT
FREQUENCY RANGE 47 ~ 63Hz
VOLTAGE RANGE 85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational )
EFFICIENCY (Typ.) 90
AC CURRENT (Typ.) 2.25A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT <1mA / 240VAC
PROTECTION
OVERLOAD 105 ~ 160% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE 30 ~ 36V
PROTECTION TYPE Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE Shut down o/p voltage, re-power on to recover
ENVIRONMENT
WORKING TEMP. -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC (Note 4)
SAFETY STANDARDS UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved; Desi gn refer to TUV EN60950-1
WITHSTAND VOLTAGE I/P-O/P:4KVAC
ISOLATION RESISTANCE I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH
EMC EMISSION Compliance to EN55032 (CISPR32) Class A, EN61000-3-2,-3
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
OTHERS
MTBF 927.6K hrs min. MIL-HDBK-217F (25)
DIMENSION 52.5*90*54.5mm (W*H*D)
PACKING 190g;60pcs/12.4Kg/0.97CUFT

General Inquiries